Centauri
®
CONDENSINGWATERBOILER
INSTALLATION & MAINTENANCE MANUAL
Models (1500, 1800, 2000) WB 250A-IFC
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND
MAINTENANCE OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER
PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS
UNIT.
TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain
important information that will help you in maintaining and operating this appliance.
Riverside Hydronics
®
, LLC
990 Haltom Road
Fort Worth, Texas 76117
1-800-990-5918
www.riversidehydronics.com
Seitenansicht 0
1 2 3 4 5 6 ... 39 40

Inhaltsverzeichnis

Seite 1 - Centauri

134-52 07/13 Centauri®CONDENSINGWATERBOILERINSTALLATION & MAINTENANCE MANUAL Models (1500, 1800, 2000) WB 250A-IFC Installation an

Seite 2

1034-52 07/13 5.5 Temperature Control Sensor The Temperature Control Sensor is coiled and secured to the control enclosure along with the Senso

Seite 3

1134-52 07/13 6.3 Gas Piping Size: Use the values in “Convert Fittings To Equivalent Straight Pipe” to add the equivalent straight pipe for each el

Seite 4 - PRODUCT SAFETY INFORMATION

1234-52 07/13 6.4 Appliance Isolation during Gas Supply Piping Pressure Test 1. The appliance and its provided manual shutoff valve must be disc

Seite 5

1334-52 07/13  All Air From Inside The Building: Each opening requires a minimum free area of 1 square inch per 1000 Btu/hr input, but not less

Seite 6

1434-52 07/13 7.3 Remote Combustion Air Cap A UL Listed air intake vent termination cap MUST be attached to the remote combustion air vent ter

Seite 7

1534-52 07/13 8.3 Maximum Category IV Vent Length (Equivalent Length) A vertical or horizontal remote Category IV vent system must be used wi

Seite 8

1634-52 07/13 8.5 Combining Category IV Vents Combined Centauri or Centauri Plus Category IV gas vent systems must incorporate an Exhausto or Tj

Seite 9

1734-52 07/13  Thermal Expansion A relief valve that discharges periodically may be due to thermal expansion in a closed system by components,

Seite 10 - 34-52 07/13

1834-52 07/13 10 TEMPTRAC™ ELECTRONIC CONTROLLER PANEL 10.1 Principle Of Operation The boiler operates to satisfy the setpoint of the TempTrac

Seite 11

1934-52 07/13 LABEL DEFAULT VALUE NET TEMPERATURE NET TEMP DETERMINED BY St1 165 165°F LED display value Hy1 -8 157°F St1 + Hy1 St4 -10 15

Seite 12

234-52 07/13 TABLE OF CONTENTS 1. Safety Considerations 2. Standard Features and Equipment 2.1. Performance 2.2. Burner, Combus

Seite 13

2034-52 07/13  C to D: Once modulation is established, the sensed loop temperature can fluctuate between 155°F and 145°F (between St4 and SR). Th

Seite 14

2134-52 07/13 10.9 LED Display Alarm Messages Alarm messages are displayed in the upper LED readout and alternate with the default display. An ala

Seite 15

2234-52 07/13 11.3 BAS connection over network with MODBUS RTU protocol (requires option ALMMB)  An optional serial connection cable (part no.

Seite 16

2334-52 07/13  Factory Default Settings - The values of the Outdoor Reset and Warm Weather Shutdown functions in the TempTrac control’s paramete

Seite 17

2434-52 07/13 12 SEQUENCE OF OPERATION 1. Incoming 120VAC a. Full time power to the Main Control Switch b. Full time power to the Variable Fr

Seite 18

2534-52 07/13 8. Delay-On Relay - Once the Delay-On (Low Fire Hold) Relay has timed out, it energizes the Modulation Release Relay (SPDT) to enable

Seite 19

2634-52 07/13 13 INITIAL STARTUP 13.1 Initial Startup Requirements Installation should be complete prior to performing initial startup; and the

Seite 20

2734-52 07/13 c. Reattach the manometer to the gas train manual shutoff valve at the burner and record the measured gas pressure in inches of wate

Seite 21

2834-52 07/13 20. After the pre-purge, the flame control energizes the HSI for the heat up period, approximately 30 seconds. At the end of that pe

Seite 22

2934-52 07/13 INLETPRESSUREMANIFOLDPRESSUREVALVE ORIFICEADJUSTMENTREGULATORADJUSTMENT Gas Train Illustration REGULATORADJUSTMENTHIGH GAS PRES

Seite 23

334-52 07/13 Warranty Forms & Wiring Diagrams Ship Separately With Each Product 9. Operatin

Seite 24

3034-52 07/13 14 TROUBLESHOOTING GUIDE Problem Probable Cause Corrective Action Starting or Pre-purge Failure Power Supply Check fuse and/o

Seite 25

3134-52 07/13 15 REPLACEMENT PARTS REPLACEMENT PARTS

Seite 26

3234-52 07/13 15.1 Control Panel 

Seite 27

3334-52 07/13 15.2 Control Panel Components (Optional components may not be included) Key No. Part No. Description Qty. U/M 1 101947 CONTROL

Seite 28

3434-52 07/13 15.3 Burner Assembly

Seite 29

3534-52 07/13 15.4 Burner Assembly and Gas Train Components Optional components may not be included) Burner Assembly Components Item Qty

Seite 30

3634-52 07/13 16 PERIODIC MAINTENANCE Listed below are items that must be checked to ensure safe reliable operations. Maintenance must be performed

Seite 31 - 15 REPLACEMENT PARTS

3734-52 07/13 6. The combustion air filter should be replaced every six months. If filter blockage becomes excessive the filter safety switch will

Seite 32 - 15.1 Control Panel

3834-52 07/13 17 RECOMMENDED MAINTENANCE SCHEDULE 1. Annual Maintenance a. Check all joints and pipe connections for tightness, corrosion or dete

Seite 33

3934-52 07/13

Seite 34 - 15.3 Burner Assembly

434-52 07/13 1. SAFETY CONSIDERATIONS  WARNING: If the information in the supplied manual(s) is not followed exactly, a fire, explosion or expos

Seite 35

4034-52 07/13 Riverside Hydronics, LLC  990 Haltom Road  Ft. Worth, TX 76117  1‐800

Seite 36

534-52 07/13 2. STANDARD FEATURES AND EQUIPMENT 2.1 Performance  Up to 94% efficiency at low fire with low return temp  Inward-fired burner t

Seite 37 - NOMINAL FILTER SIZE

634-52 07/13 3 PRODUCT DESCRIPTION Component, Controls and Connection Locations (Locations May Vary)

Seite 38

734-52 07/13 4 BOILER INSTALLATION 4.1 Checking Equipment Before You Install Inspect the unit completely upon receipt from the freight carrier

Seite 39

834-52 07/13 4.6 Clearances To Combustible Surfaces Minimum 1" clearance must be provided from any vent surface to adjacent combustible m

Seite 40 - Riverside Hydronics

934-52 07/13 1. Installing the boiler on a 4 inch to 6 inch housekeeping pad is recommended to ensure proper condensate drainage. 2. Use 3/4” CP