The TIER 1 SYSTEM STATUS screen is provided to monitor the most commonly need system
informationformultipleboiler.Thefirstscreendisplaythisinformationforuptoeightboileranda
supplementalscreenTIER 1912displaysthesameinformationforboilers9to12.
SYSTEM
TEMPdisplaysthecurrentsystemtemperature.
OUTDOOR TEMP displays the
currentsystemtemperature.
ADJUSTED SETPOINT displays the
set point after a reset function
such as Outdoor Reset, Scheduled
Setbackor Remot eSetpoint
adjustment have been made. This
is the same parameter as is
locatedontheTier1menu.
SETPOINT is the current
set point
foreachboilerinthesystem.
INLETthisisthecurrentmeasuredreturnwatertemperatureofeachboiler inthesystem.
OUTLETthisisthecurrentmeasuredsupplywatertemperatureofeachboilerinthesystem.
The OUTLET temperature displays can be turned off when not used
as shown here by
touchingthedisplay.
Thenumericaldisplayboxeslocatedatthebottomofthescreenindicatedthetimeelapsed
asthe controlcountsuptoenabletherespectiveboiler (top)or downtodisable (bottom).
ThetotaltimeisenteredonOPTIONSCREEN1.
Thereis
aTIER2SYSTEMSTATUSscreenwhichprovidesthesameinformationfortheTier2boilers
withaddressesfrom13to20.
TIER 1 SYSTEM S
T
ATU
S